Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL01874
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06EL01874 9/26/06 1. Provide fault current rating of existing fused disconnects, and AFC at those disconnects. If AFC exceeds rating provide new equipment. This may be addressed by adding a reference to these existing disconnects in the note instructing the contractor to verify AFC. 2. Provide locations for electrical loads on the load side of the existing feeders, and identify the nature of these loads (panels, motors?). Provide year of construction of panels and branch circuit breakers. For any panels which have overcurrent protective devices manufactured before the early 1990s, disregard because they will take longer to open than the feeder CBs. |