Permit Number: T06EL01874
Parcel: 12415016A

Address:
840 E 17TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01874
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06EL01874 9/26/06

1. Provide fault current rating of existing fused disconnects, and AFC at those disconnects. If AFC exceeds rating provide new equipment. This may be addressed by adding a reference to these existing disconnects in the note instructing the contractor to verify AFC.
2. Provide locations for electrical loads on the load side of the existing feeders, and identify the nature of these loads (panels, motors?). Provide year of construction of panels and branch circuit breakers. For any panels which have overcurrent protective devices manufactured before the early 1990s, disregard because they will take longer to open than the feeder CBs.