Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01719
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL01719 9/7/06

1. 14.4A would be 1728 VA, not 1440.
2. The total VA counts for Phases A and B need to be divided by 120 to get amperage. For example, Phase A would be 197A, not 99A.
3. Please account for continuous loads and largest motors in the load calculations. If 1.25 were to be multiplied by each lighting load, this panel would be overloaded.