Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06EL01719
Parcel: 12704037B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01719
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL01719 8/28/06

1. Provide a local disconnecting means for the window screens.
2. Add the additional window screen as discussed in out telephone conversation.
3. Provide the power requirements for the window screens.
4. Demonstrate that the panel is not being overloaded with the additional electrical load.