Review Details: ELECTRICAL
Permit Number - T06EL01710
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06EL01710 8/25/06 1. Please add Zoning and Engineering to the WorkFlow. 2. Please provide manufacturer certification that operating this generator using only 2 phases out of 3 will not violate its listing. 3. Generator output is 208/120V. Please provide voltage of all equipment intended for generator power. 4. Provide overcurrent protection for generator and feeder. Reference NEC 445.12. 5. Since the generator can only supply 104A, at a power factor of 0.8. provide load calculations. Reference 200A main. 6. Provide rating of the transfer switch. |