Review Details: ELECTRICAL
Permit Number - T06EL01708
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1- In the tap to the Mini Power Center, change the #10 GND to a #8 GND. Reference NEC Table 250.120. 2- In the conduit between the TEP transformer and the gutter, change the #4GND to a #2GND. Please note that this is correct on the Cable schedule but not on the Line Diagram. Same with the nipple between the two gutters. 3- Please identify the scope of work for this location on the Title Sheet. |