Permit Number: T06EL01707
Parcel: 128100270

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01707
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. In the tap to the Air Compressor, change the #12 GND to a #6 GND. Reference NEC Table 250.120.
2- In the tap to the Mini Power Center, change the #10 GND to a #6 GND. Reference NEC Table 250.120.
3- Please identify the scope of work for this location on the Title Sheet.