Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL01707
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. In the tap to the Air Compressor, change the #12 GND to a #6 GND. Reference NEC Table 250.120. 2- In the tap to the Mini Power Center, change the #10 GND to a #6 GND. Reference NEC Table 250.120. 3- Please identify the scope of work for this location on the Title Sheet. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/12/2006 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/12/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |