Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL01705
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Sheet 6 Note #10 and Sheet 9 Note 2 state that Owner will install lighting and convenience receptacles in the electrical room. If this is to be done under a separate permit, please indicate this on the plans. Otherwise, add the fixtures and outlets to the plans for the room and panel schedule. 2. Sheet 9 Note 4 states that Owner will fill in blockouts in walls and floor and install AC in electrical room. If this is to be done under a separate permit, please indicate this on the plans. Otherwise, Building and Mechanical will have to be added to the WorkFlow. The Permit Clerks can do this for you. 3. It appears that the intent is to put Keynote 12 on Sheet 25 by the fused disconnect protecting the feeder to the New Mini Power Zone. Please clarify. |