Permit Number: T06EL01466
Parcel: 110064070

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01466
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL01466 8/17/06

1. On the One-Line Diagram, it appears that the "600 A" needs to be changed to read: "800 A."
2. There are 35 address designations associated with this permit. There are greater than this number on the freshly generated site plan. We need to know exactly which units are in this scope of work, and have them identified such that there is a correspondence among these electrical plans, the address/meter identifiers in the Permit Application, and the intent of the Owner.
3. See the Building Plans Examiner regarding the accessibility needs in the conversion from apartments to condos.