Permit Number: T06EL00850
Parcel: 113041410

Address:
3316 N 1ST AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00850
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL00850 5/5/06


2. Provide a site drawing, with project address, and location of new and existing equipment.
3. Provide a complete electrical line diagram, with conduit and conductor size and type, new and existing equipment, size and type of overcurrent protective devices, grounding electrode system.
4. Provide TEP available fault current, fault current rating of all equipment, and available fault current at new service and panels.
5. If there are any load changes, plans shall be prepared by a Registered Electrical Engineer or Architect.