Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06EL00847
Parcel: 113041410

Address:
3318 N 1ST AV

Review Status: Active

Review Details: ELECTRICAL

Permit Number - T06EL00847
Review Name: ELECTRICAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2006 ANY ELECTRICAL-COMMERCIAL REVIEW Active