Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00836
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06EL00836 5/3/06 1. Inconsistency of circuit size among sheets. Please clarify. 2. Specify conduit and conductor size and type. 3. Provide disconnect per NEC 600.6. 4. Provide sign specifications/cut sheets. 5. Account for the existing 20A circuit on panel schedule. 6. Provide load calculations for panel. |