Permit Number: T06EL00658
Parcel: 115070750

Address:
1742 N ORACLE RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00658
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide the available fault current with calculations.Indicate at single line diagram at each building service.2.Probvide fuse types at all service disconnects.3.Provide a grounding schematic for all buildings singgle line diagram.Include grounding electrodes(if utilized),water-gas-building steel bonding,size of bond & grounding electrode conductors.4. Size gutters to accomodate the size of conductors (min. bending radius).

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
04/28/2006 SUE REEVES REJECT SHELF Completed