Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00658
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide the available fault current with calculations.Indicate at single line diagram at each building service.2.Probvide fuse types at all service disconnects.3.Provide a grounding schematic for all buildings singgle line diagram.Include grounding electrodes(if utilized),water-gas-building steel bonding,size of bond & grounding electrode conductors.4. Size gutters to accomodate the size of conductors (min. bending radius). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/28/2006 | AMERY KLAPPERT | OUT TO CUSTOMER | Completed |
04/28/2006 | SUE REEVES | REJECT SHELF | Completed |