Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL00580 4/4/06

1. Take permit application to Permit Clerks, and have them add Zoning, Engineering, Signs, and Building to the WorkFlow.
2. Provide a cut sheet of the transformer and flourescent lights.
3. Provide panel and circuit number for the sign.
4. Plot location of the transformer and electrical panel on the plans.
5. Specify conduit and conductor size and type.