Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00580
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06EL00580 4/4/06 1. Take permit application to Permit Clerks, and have them add Zoning, Engineering, Signs, and Building to the WorkFlow. 2. Provide a cut sheet of the transformer and flourescent lights. 3. Provide panel and circuit number for the sign. 4. Plot location of the transformer and electrical panel on the plans. 5. Specify conduit and conductor size and type. |