Review Details: ELECTRICAL
Permit Number - T06EL00556
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/29/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/06/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00556 4/6/06 1. Provide a scaled site plan showing property lines, existing buildings, and new equipment. If location for end-use equipment has not been determined, note "to be determined" on the plans. 2. Not a Code-issue, but you may want to give consideration to GFCI protection on the exterior receptacles. 3. Please note that Primary is drawing 39A, not90A. 4. Panel ML does not need to be series rated, but if so, specify line side and load side devices, and line side and load side OCPD values. 5. 4.8 KAIC at service disconnect does not appear to be a sinsible value. 6. The #6 GND between the meter can and the service disconnect is redundant. Please eliminate. |