Review Details: ELECTRICAL
Permit Number - T06EL00503
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T96EL00503 5/17/06 1. Add Building and Engineering to WorkFlow. The Permit Clerks can do this for you. 2. Provide a disconnect within sight of the controllers. Reference NEC 430.102 (A). 3. Specify feeder and service. It appears the intent is to use Keynotes 8 and 9 to this end, but that has not been done. 4. Provide overload protection for the 1/2 HP motors, unless thermally protected. |