03/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t06el00502 3/23/06


1. Reference NEC 230.3 Number of Services, a building shall be provided with only one electrical service unless otherwise allowed by this Code section. Plans Examiner and Building Official do not accept reference to 230.3 (D).
2. Provide sufficient documentation to demonstrate compliance with NEC 255 Part III. Plans Examiner and Building Official do not accept reference to 225.30 (D).