Permit Number: T06EL00502
Parcel: 11918029D

Address:
1310 W AJO WY 2M

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00502
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t06el00502 3/20/06

1. Please provide total number of occupants each building may have, and total square footing of each building upon which new lighting fixtures are to be mounted. If the occupancy is 20 or above or if the SF exceeds 3000, the plans shall be prepared and sealed by a registered Engineer or Architect in the State of Arizona.
2. Reference NEC 230.3 Number of Services, a building shall be provided with only one electrical service unless otherwise allowed by this Code section. Provide sufficient documentation on the drawings to demonstrate compliance.
3. Provide sufficient documentation of the drawings to demonstrate compliance with NEC 225 Part II.
4. Provide documentation that existing fixtures are of the full cutoff lighting distribution.