Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00434
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06EL00434 4/3/06 1. House load calculations may not use demand factors in NEC 220.30. This Code Section applies only to dwelling units. 2. Please verify that there are no fixed-in-place appliances, heating, or air conditioning loads in the dwelling units. Reference NEC 220.30 (B) (3) & (C). 3. For main electrical load calculations, demand factor of 40 % may not be taken again. The correct Code section for Feeder and Service Load is NEC 220.32. 4. House loads shall be added to the total computed according to the requirements of NEC 220.32 (C). Reference NEC 220.32 (B). 5. This building totals 3749 SF. As such this electrical design shall be executed and sealed by an Electrical engineer or Architect registered in the State of Arizona. 6. Minimum font size 1/8". 7. Submit plans with both sheets the same size. 8. Provide overcurrent protective devices for the panels and their feeders. 9. Show the locations of the panels on the plans. 10. Provide the rating of the panels. 11. Main Electrical Load Calculations call for 200A main service disconnect. Riser diagram calls for 400A all-in-one. Please clarify. Electrical Plans Examiner will verify compliance with NEC 250.66 in a subsequent submittal. 12. Provide available fault current at service. 13. Provide fault current rating of all new and existing equipment. |
| 04/03/2006 | HEATHER THRALL | ZONING | REVIEW | Approved |