Permit Number: T06EL00370
Parcel: 12007255B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00370
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06EL00370 2/24/06

1. Provide TEP available fault current.
2. Provide fault current rating of new and existing equipment.
3. Provide fault calculations as necessary.
4. Demonstrate that building is less than 3000 SF and occupancy is less than 20, or have a Registered Architect/Engineer prepare the plans.