Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00370
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06EL00370 2/24/06 1. Provide TEP available fault current. 2. Provide fault current rating of new and existing equipment. 3. Provide fault calculations as necessary. 4. Demonstrate that building is less than 3000 SF and occupancy is less than 20, or have a Registered Architect/Engineer prepare the plans. |