Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06EL00321
Parcel: 117021250

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00321
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00321 12/14/07

1. Clarify position of panel on plans. Not legible.
2. If the device referred to as "Sub Main is an electrical service disconnect, with panel and metering as a self-contained unit, it would not be a sub-main. Termology is misleading.
3. Provide electrical requirements for the gate operator.
4. Provide a disconnecting means for the gate operator per NEC 430.
5. Need manufacturer documentation of mean lumens per lighting fixture.
6. Note that Table 5.1 of the Tucson Lighting Code has a limit of 12,000 Mean Lumens per Watt.
7. This plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer.