Review Date Reviewer's Name Type of Review Description Status Comments
12/14/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM00321 12/14/07

1. Clarify position of panel on plans. Not legible.
2. If the device referred to as "Sub Main is an electrical service disconnect, with panel and metering as a self-contained unit, it would not be a sub-main. Termology is misleading.
3. Provide electrical requirements for the gate operator.
4. Provide a disconnecting means for the gate operator per NEC 430.
5. Need manufacturer documentation of mean lumens per lighting fixture.
6. Note that Table 5.1 of the Tucson Lighting Code has a limit of 12,000 Mean Lumens per Watt.
7. This plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer.