Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00321
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/14/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM00321 12/14/07 1. Clarify position of panel on plans. Not legible. 2. If the device referred to as "Sub Main is an electrical service disconnect, with panel and metering as a self-contained unit, it would not be a sub-main. Termology is misleading. 3. Provide electrical requirements for the gate operator. 4. Provide a disconnecting means for the gate operator per NEC 430. 5. Need manufacturer documentation of mean lumens per lighting fixture. 6. Note that Table 5.1 of the Tucson Lighting Code has a limit of 12,000 Mean Lumens per Watt. 7. This plan should be designed and sealed by an Arizona Registered Professional Electrical Engineer. |