Permit Number: T06EL00280
Parcel: Unknown

Address:
2008 E RIVER RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00280
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T06EL00280 2/10/06

1. Provide TEP available fault current.
2. Provide fault current rating of All-in-One.
3. Show electrical loads, such as receptacles, and their circuit breakers, conduit and conductors.
4. Show sizing of the Grounding Electrode Conductor and the Main Bonding Jumper.