Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00280
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06EL00280 2/10/06 1. Provide TEP available fault current. 2. Provide fault current rating of All-in-One. 3. Show electrical loads, such as receptacles, and their circuit breakers, conduit and conductors. 4. Show sizing of the Grounding Electrode Conductor and the Main Bonding Jumper. |