Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06EL00030 2/27/06 I'm told that Panel L is a 200A panel, but that is not evident from the plans. If it exceeds 200A, either the load it draws and in either its OCPD or rating, it would not be in compliance with the 10' tap rule NEC 240.20 C 2, per the review comment. Second item: the arrowhead from the note "4-350 MCM 1/0 GND" has been eliminated. If the intent is to have that note pertain to the run between the gutter and CT Can, the 1/0 GND would be redundant because the N-G bond is to take place in the service disconnects per NEC 250.24 (B). |