Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06EL00030
Parcel: 12905139A

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL00030
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL00030 1/18/06

1. Provide the rating of panel L such that compliance with NEC 240.20 (C) (2) may be evaluated.
2. Specify feeder overcurrent protective devices.
3. Specify line side and load side ratings of Panel H with its remote OCPD.
4. Address AFC with respect to the Ice Machine. Suggest an RK-1 device.