Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00030
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06EL00030 1/18/06 1. Provide the rating of panel L such that compliance with NEC 240.20 (C) (2) may be evaluated. 2. Specify feeder overcurrent protective devices. 3. Specify line side and load side ratings of Panel H with its remote OCPD. 4. Address AFC with respect to the Ice Machine. Suggest an RK-1 device. |