Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM06560
Parcel: 11005014C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM06560
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The introduction of untempered make-up air into the kitchen has proven to be an unsafe sitution due to occupants disabling or blocking the introduction of the air during cold weather. This adversly affects the operation of the exhaust system posing a danger to the occupants. Revise the make-up air system to comply with Section 508.1, IMC 2003.
02/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/02/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2007 DELMA ROBEY OUT TO CUSTOMER Completed