Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The introduction of untempered make-up air into the kitchen has proven to be an unsafe sitution due to occupants disabling or blocking the introduction of the air during cold weather. This adversly affects the operation of the exhaust system posing a danger to the occupants. Revise the make-up air system to comply with Section 508.1, IMC 2003.
02/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
02/02/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2007 DELMA ROBEY OUT TO CUSTOMER Completed