Permit Number: T06CM06560
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06560
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
01/03/2007 ROBERT SHERRY WATER REVIEW Approved
01/03/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm the size of the waste piping for the existing grease trap. Show the location of the grease trap on the plans.
2. Limit the hot water supply to the lavatory to 110 degrees Fahrenheit.
3. Provide the developed length for the gas piping and all of the attached loads.
4. Revise the total amount of outside air per footnote (f) of Table 403.3, IMC 2003 (1.5x the floor area of the kitchen).
01/03/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide make up air for the kitchen hood.
01/24/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/24/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/24/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2007 DELMA ROBEY OUT TO CUSTOMER Completed