Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2007 SEPTIC APPROVAL WWM REVIEW Denied DEQ NEED PERC, DESIGN & FEE FOR SEPTIC REVIEW
02/12/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied February 12, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Fowler Residence
CITY OF TUCSON LOG NO. T06CM06541
WILLDAN PROJECT NO. 13881-7006 – 1ST REVIEW

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
SFR
Porch N/A V-B 1736
560 No Smoke

Special Inspection is required for the following items:

The following items are acceptable for deferred submittals:
Trusses

GENERAL COMMENTS:
General
A deferred submittal letter for trusses will need to be forwarded directly to the Building Official and approved. Reference the City of Tucson Submittal Policy.

All Sheets
All lettering should be a minimum of 1/8” high capitalized. Reference the City of Tucson Submittal Requirements.

ARCHITECTURAL COMMENTS:
Sheet 2
Please provide cut sheets for the fireplace stove. Reference 2003 IRC Section 106.1.1.

STRUCTURAL COMMENTS:
Sheet 3
All slabs and pads, including landings at all doors, shall be shown and their thickness specified. Reference IRC Sections R506.1, 403.1.

Indicate the slope for exterior slabs. Reference IRC Section R311.6.1.

Specify design criteria on plans. Provide values for floor dead load and live load, as well as roof dead load and live load. Reference IRC Sections R301.4 and R301.5.

Sheet 4
Specify lumber grade and species. Specify manufacturer and series on glue-lams and “I” joists. Reference IRC Section R106.1.1.

PLUMBING COMMENTS:
Sheet 8
Note and specify all piping materials. Reference UPC Section P2608.1.

MECHANICAL COMMENTS:
Reviewed and accepted.

ELECTRICAL COMMENTS:
Sheet 11
Please provide cut sheets and calculations for all exterior lighting fixtures. Reference the City of Tucson Outdoor Lighting Code.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference the City of Tucson Submittal Requirements.

ENERGY CODE COMMENTS:
Sheet 2
Indicate on the plan the “R” values of insulation, as well as the “U” values of the windows, skylights, and doors in compliance with the energy calculations provided or prescriptive requirements of Chapter 11. Reference IRC Section R106.1.1.

Please submit the required energy code calculations by using the “RES” check program, Chapter 11 of the IRC, or the 2003 IECC, and also annotate on the plans. Reference IRC Section R106.1.1.

Sheet 10
Annotate on the plans that any ductwork installed in unconditioned space will have a minimum of R-5 insulation, and any ductwork installed outside the building envelope will have a minimum of R-8 insulation. Reference IRC Section N1103.32.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.

Sincerely,

WILLDAN


Martin Haeberle, C.B.O.
Building Official

MAH/tb