Permit Number: T06CM06511
Parcel: 133160500

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06511
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1)PROVIDE JUSTIFICATION FOR OCCUPANT LOAD AND FIXTURE COUNT. PROVIDE SQ. FOOTAGE OF AREAS FOR DINING,STANDING, KITCHEN, BAND SETUP, ETC. IT APPEARS DANCE FLOOR AREA HAS BEEN EXPANDED. PLEASE PROVIDE SEATING LAYOUT ON FLOOR PLAN.
2) PROVIDE EXIT LIGHTING CLARIFYING EXIT PATH.
01/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Directly connect the handwashing sinks to the building drain.
2. Indirect waste lines over 15 feet in length (i.e. the 3-compartment sink at the bar) require a trap and an independent vent through the roof.
01/02/2007 ROBERT SHERRY WATER REVIEW Approved
01/16/2007 CAGUILA1 ZONING REVIEW Needs Review
01/16/2007 CAGUILA1 WWM REVIEW Needs Review
01/16/2007 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/16/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
01/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/16/2007 CAGUILA1 FIRE REVIEW Needs Review