Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06418
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 01/03/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a vent for the clothes dryer. |
| 01/03/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vent for the flow control device. 2. Provide an upper terminal cleanout for the existing 4" building drain. 3. Provide a cleanout downstream of the grease trap. 4. Revise the size of the cleanout for P-10 to match the size of the drain pipe. 5. Revise the size of the inlet and outlet pipe on the grease trap from 2" to 3". 6. Revise the size of the condensate drain downstream of AC-5 to 1". |
| 01/03/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/03/2007 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/03/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 01/03/2007 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 01/03/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 01/03/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/28/2006 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/03/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/03/2007 | DELMA ROBEY | REJECT SHELF | Completed |