Permit Number: T06CM06408
Parcel: 12419037C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T06CM06408
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Passed
12/20/2006 MICHAEL ST. PAUL ZONING REVIEW Passed
12/20/2006 LOREN MAKUS ENGINEERING REVIEW Approved
12/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t06cm06408 12/20/06

1. Outdoor Lighting Lumen Calculation was based upon the allowable lumen count for Option 1, that is, mostly LPS. This appears to be all HPS. Please note that the area is E3, not E2.
2. Please place the following note on the plans: "Contractor shall provide TEP available fault current before final electrical clearance."

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2007 CINDY AGUILAR OUT TO CUSTOMER Completed