03/07/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T06CM06405
Date 3/7/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references.

FOUNDATION PLANS:
1. Indicate depth of garage post footing (Detail 14/A-3)
2. Show a landing or floor surface at the exterior door on the garage. Landings must be at least as wide as the doors they serve and 36" in the direction of travel, R311.4.3.
3. Show compliance with termite treatment specified by R320, as amended.

STRUCTURAL PLANS:
1. Justify garage GLB. Our program indicates 30% deficiency.
2. Completely detail all connections to the foundation and/or framing members:
Rafter to top plate (Roof tie-down per R802.11)
Beam to post (Specify post size and connections to beam and plate)
Ledger to masonry fireplace (Lag bolt spacing)
Joist to ledger at fireplace
Hanger type for GLB (Detail 8/A-4)
Framing under CS16 (Detail 8/A-4)
Continuous load path for shear transfer
Sister connections for rafters (Rear Porch)
Outrigger connections to the structure (West Garage wall)
3. Show masonry wall vertical lateral support R606.8.2 (Detail 4/A-3).

SECTIONS - DETAILS - MISC. NOTES:
1. Cross-sections shall be cross-referenced to the floor plan and framing plans.


If you have any questions, please contact your assigned plans examiner:
Clayton Trevillyan
791-5550 ext. 1113

Final Status

Task End Date Reviewer's Name Type of Review Description
03/13/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
03/13/2007 SUE REEVES REJECT SHELF Completed