Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06388
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/18/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/18/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 01/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06388 1/19/07 1. Provide panel schedules and panel load calculations. 2. Line diagram shall go on full size plans. 3. Indicate location of all electrical equipment on plans. 4. Provide voltage and phase of electrical service. 5. Provide voltage, phase, and fault current rating of new panel. 6. Provide fault calculations. |
| 01/19/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/15/2007 | FSANCHE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/15/2007 | FSANCHE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 02/15/2007 | FSANCHE1 | WATER | REVIEW | Needs Review | |
| 02/15/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/15/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |
| 02/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |