Permit Number: T06CM06383
Parcel: 114600750

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM06383
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2007 ROBERT SHERRY WATER REVIEW Approved
01/24/2007 DAVE MANN FIRE REVIEW Approved
01/29/2007 GERRY KOZIOL WWM REVIEW Approved
01/31/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/05/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Tanque Verde Place - Lots 50, 51 & 52
T06CM06381, T06CM06382 & T06CM06383
Building Plan (1st Review)

TRANSMITTAL DATE: February 5, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. The tentative plat/development plan needs to be stamped as a site plan. This can be done as a walk through. Once the site plan has been approved include two (2) copies of the approved site plan with your next building plan submittal.

3. Provide a dimension from the proposed buildings to the back of curb along Avienda Valiente on the partial site plan.

4. Zoning is willing to do an over the counter review once the tentative plat/development has been stamped as a site plan.

5. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180.

C:\planning\building\t06cm06381.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved and stamped site plan and additional requested documents
02/06/2007 LAITH ALSHAMI ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2007 DELMA ROBEY OUT TO CUSTOMER Completed
02/07/2007 SUE REEVES REJECT SHELF Completed