Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2007 HEATHER THRALL ZONING REVIEW Approved
01/19/2007 ANY ENGINEERING REVIEW Approved
01/22/2007 MARTIN BROWN FIRE REVIEW Approved
01/22/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06369 1/22/07

1. Provide disconnect for gate motors. Reference NEC 430 Part IX.
2. Account for all 4 gates on the panel schedule.
3. Provide cut sheets for the gates and power requirements.
4. Provide overcurrent protection for the panel feeder. Reference NEC 240.
5. Provide conduit and conductor size and type for feeder.
6. Show proper phase distribution on panel. See NEC 408.3 (E) and the attached.
7. Put electrical on full sized plans.