Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM06369
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 01/19/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 01/22/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/22/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06369 1/22/07 1. Provide disconnect for gate motors. Reference NEC 430 Part IX. 2. Account for all 4 gates on the panel schedule. 3. Provide cut sheets for the gates and power requirements. 4. Provide overcurrent protection for the panel feeder. Reference NEC 240. 5. Provide conduit and conductor size and type for feeder. 6. Show proper phase distribution on panel. See NEC 408.3 (E) and the attached. 7. Put electrical on full sized plans. |
| 02/14/2007 | FSANCHE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |