Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM06349
Parcel: 13348128F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06349
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2007 SREEVES1 WATER REVIEW Needs Review
12/15/2006 TERRY STEVENS ZONING REVIEW Approved
12/15/2006 LOREN MAKUS ENGINEERING REVIEW Approved
12/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06349 12/20/06

1. Minimum font size is 1/8". Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide conductor size for Ckt C8-8, C8-38,40,42. Reference NEC 240.4 (D).
3. Identify panel and circuit for the mop sink load.
4. Walk-In Freezer load tabulations and voltage do not conform to the description on Sheet SP-1. Please coordinate with kitchen equipment electrical requirements for this piece of equipment, and for all others on this project which may apply.
5. Ckt C8-3 appears to have 1988 VA, not 900. Considering continuous loading, the 20 circuit would be overloaded.
6. Provide a maintenance receptacle for HP-1.
12/20/2006 DAVE MANN FIRE REVIEW Approved
12/26/2006 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/26/2006 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Denied
12/26/2006 CAGUILA1 WWM REVIEW Needs Review
12/26/2006 JWILLIA5 BUILDING-COMMERCIAL REVIEW Needs Review
12/26/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review