Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM06329
Parcel: 12607033C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM06329
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/17/2007 SREEVES1 ENGINEERING REVIEW Needs Review
04/17/2007 ROBERT SHERRY WATER REVIEW Approved
04/17/2007 SREEVES1 ZONING REVIEW Needs Review
04/17/2007 SREEVES1 WATER REVIEW Needs Review
04/17/2007 MARTIN BROWN FIRE REVIEW Denied Lodge on the Desert

1. The exits from the hotel buildings second floor are not 1/3 of the diagonal distance apart. IFC Chapter 10.
2. Show the distance between the exterior stairs and the adjacent buildings.



Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2007 SUE REEVES OUT TO CUSTOMER Completed