Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM06329
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 04/17/2007 | SREEVES1 | ENGINEERING | REVIEW | Needs Review | |
| 04/17/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/17/2007 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 04/17/2007 | SREEVES1 | WATER | REVIEW | Needs Review | |
| 04/17/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Lodge on the Desert 1. The exits from the hotel buildings second floor are not 1/3 of the diagonal distance apart. IFC Chapter 10. 2. Show the distance between the exterior stairs and the adjacent buildings. Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/17/2007 | SUE REEVES | OUT TO CUSTOMER | Completed |