| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/08/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 12/15/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06309 12/15/06 1. WH-2 is 240V according to the Plumbing Fixture Schedule. Has 208V power. Please clarify. 2. WH-2 draws 32A according to the Plumbing Fixture Schedule. Is on a 30A circuit. Please clarify. 3. On the Electrical Lighting Plan, there are two connections which appear to place all of the lights on the same circuit. Please correct/eliminate. 4. Please add the following note in a prominent place on the plans: "All work in patient care areas shall comply with the requirements of NEC 517.13." |
| 12/15/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/15/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 12/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a vent for the clothes dryer. |
| 12/15/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how WH-1 is limited to a maximum water temperature of 110 degrees Fahrenheit. 2. Condensate from an A/C unit may not be directly connected to the tailpiece of washer box. |
| 12/15/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/15/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/15/2006 | DAVE MANN | FIRE | REVIEW | Approved |