Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/08/2007 CAGUILA1 WWM REVIEW Needs Review
12/15/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06309 12/15/06

1. WH-2 is 240V according to the Plumbing Fixture Schedule. Has 208V power. Please clarify.
2. WH-2 draws 32A according to the Plumbing Fixture Schedule. Is on a 30A circuit. Please clarify.
3. On the Electrical Lighting Plan, there are two connections which appear to place all of the lights on the same circuit. Please correct/eliminate.
4. Please add the following note in a prominent place on the plans: "All work in patient care areas shall comply with the requirements of NEC 517.13."
12/15/2006 ROBERT SHERRY WATER REVIEW Approved
12/15/2006 TERRY STEVENS ZONING REVIEW Approved
12/15/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a vent for the clothes dryer.
12/15/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how WH-1 is limited to a maximum water temperature of 110 degrees Fahrenheit.
2. Condensate from an A/C unit may not be directly connected to the tailpiece of washer box.
12/15/2006 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/15/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
12/15/2006 DAVE MANN FIRE REVIEW Approved