Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T06CM06305
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/21/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06CM06305 12/18/06 1. Provide written permission from the Registrant who sealed the model plans, allowing the annotation of the Interconnect Diagram to modify the wording: "Customer Main AC Service Panel" to read: Customer Sub-Panel, for this particular address. 2. Provide the placards required by NEC 690.56 (B). PROVIDE THE EXACT WORDING ON THE PLANS. 3. Note that the lack of disconnecting means to the house may be in violation of NEC 225.31. |