Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM06303
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (152 fixture units equates to a demand of 55 GPM) |
| 11/06/2007 | DAVE MANN | FIRE | REVIEW | Denied | Incorrect design criteria for sprinkler system on sheet P 1. If these shops are to be used for retail sales, the hazard classification should Ordinary Group II, with a density of 0.20 over 1500 sq. ft. Also, please include flow data (static pressure, residual pressure, and GPM). This data is available from the Systems Engineering section of the fire department. The number is 791-3234. |
| 11/07/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | 11/07/07 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |
| 11/13/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/13/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | Submit approved site plan with building plan. |
| 11/15/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | NEEDS 8TH FLOOR REVIEW & APPROVAL MANHOLE TAP PERMIT (AGAINST FLOW) CLEAN OUT IN R.O.W. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/04/2007 | DELMA ROBEY | REJECT SHELF | Completed |