Review Details: COMMERCIAL TI

Permit Number - T06CM06291
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/13/2006 ROBERT SHERRY WATER REVIEW Approved
12/14/2006 MICHAEL ST. PAUL ZONING REVIEW Approved
12/14/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06291 12/14/06

1. Ductless Air Conditioning Unit Schedule calls for Minimum Fuse Size of 15A. That fuse shall be provided for each unit.
2. Document the substantiation why the Available Fault Current at the new panel is less than 10,000A. For example, if the feeder panel is rated at 10K, if previously approved and sealed drawings document it as such, etc.
12/18/2006 DROBEY1 WWM REVIEW Needs Review
12/18/2006 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
12/18/2006 DROBEY1 ENGINEERING REVIEW Needs Review
12/18/2006 DROBEY1 FIRE REVIEW Needs Review
12/18/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review