| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/14/2006 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/14/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06291 12/14/06 1. Ductless Air Conditioning Unit Schedule calls for Minimum Fuse Size of 15A. That fuse shall be provided for each unit. 2. Document the substantiation why the Available Fault Current at the new panel is less than 10,000A. For example, if the feeder panel is rated at 10K, if previously approved and sealed drawings document it as such, etc. |
| 12/18/2006 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/18/2006 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/18/2006 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
| 12/18/2006 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 12/18/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |