Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide a dimension floor plan clarifying cooridor widths.
2) Clarify scope of work completed without permits per inspection report issued from denied C of O and last approved floor plan. (From rear corridor to front of cash register is new) Provide electrical, plumbing, and mechanical plans accordingly.
3) Clarify occupant load.
4) Justify 20% cost of construction spent towards accessibility see section 3409.6 provide breakdown of cost and items on drawings.
4)
12/13/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide additional information to clarify the operation of the two Type I hoods and the make up air (e.g. air flow rates for each). Indicate the required amount of outside air to be provided by the roof top unit.
12/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06288 12/13/06

1. Provide panel and circuit number for all new electrical loads.
2. Provide full panel schedule and load calculations.
3. Clarify electrical connections, that is plug-in vs. hard-wired.
4. Provide disconnects for appliances. Reference NEC 422 Part III.
12/13/2006 ROBERT SHERRY WATER REVIEW Approved
12/13/2006 ANY ZONING REVIEW Active
12/13/2006 ANY WWM REVIEW Active
12/13/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide additional information to evaluate the drain piping for the kitchen and the gas piping.
12/13/2006 ANY ENGINEERING REVIEW Approved
12/13/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
12/13/2006 ANY FIRE REVIEW Active