Permit Number: T06CM06270
Parcel: 136238620

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T06CM06270
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2007 JAY HOGAN COMMUNICATIONS REVIEW Approved
12/14/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/20/06
ACTIVITY NUMBER: T06CM06270

PROJECT NAME: Cell Tower
PROJECT ADDRESS: 6310 E. Golf Links
ARCHITECT / ENGINEER: John Erion
PROJECT REVIEWER: Christy Foreman


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) Per structural calculations - Design check summary for foundation Engineer specifies 54" diameter concrete pier. Sht. F-1 specifies 48" diameter concrete pier.
2) Provide drawing for monopole justified in structural calculation clarify dimension / size that has been justified.
3) Provide mounting height of antennas and provide details for connections of antennas to monoploe.
4) Provide structural calculations for 8'-0" screen wall..
12/19/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. The existing unknown lighting fixtures need to be accounted for on the plans. If the existing site lighting is being modified less than 10%, Section 8.1.5 of the Tucson Lighting Code allows the schedule to be waived in lieu of a statement documenting such by the Registrant. This may be helpful if the site fits these criteria.
2. Please note that if all lighting is full-cutoff, it is permissible to utilize Option 2 on Table 5.1.
3. Please eliminate the redundant ground between the service disconnect and the utility transformer.
4. Please note that Tucson Electric Power Company does not typically provide a 208V, single phase service. Suggest a check with the Developer for this area if this has not already been done.
12/20/2006 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Denied Special Exception condition #3 for case SE-06-38 specifies that the maximum pole diameter shall be 18 inches. The maximum pole diameter on the drawings and details scales to almost two (2) feet (twenty-four inches). Revise plans to demonstrate compliance by adding a note to the plans stating that the maximum pole diameter shall be 18 inches, and revise dimensions of the "monopalm" in all drawings/details accordingly.
12/20/2006 TERRY STEVENS ZONING REVIEW Denied 12/20/06

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The Cell Tower site plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section of DSD.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
02/15/2007 CINDY AGUILAR REJECT SHELF Completed