Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T06CM06270
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2007 | JAY HOGAN | COMMUNICATIONS | REVIEW | Approved | |
| 12/14/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 12/20/06 ACTIVITY NUMBER: T06CM06270 PROJECT NAME: Cell Tower PROJECT ADDRESS: 6310 E. Golf Links ARCHITECT / ENGINEER: John Erion PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CHRISTY.FOREMA1@TUCSONAZ.GOV IF YOU CARE TO DISCUSS. 1) Per structural calculations - Design check summary for foundation Engineer specifies 54" diameter concrete pier. Sht. F-1 specifies 48" diameter concrete pier. 2) Provide drawing for monopole justified in structural calculation clarify dimension / size that has been justified. 3) Provide mounting height of antennas and provide details for connections of antennas to monoploe. 4) Provide structural calculations for 8'-0" screen wall.. |
| 12/19/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. The existing unknown lighting fixtures need to be accounted for on the plans. If the existing site lighting is being modified less than 10%, Section 8.1.5 of the Tucson Lighting Code allows the schedule to be waived in lieu of a statement documenting such by the Registrant. This may be helpful if the site fits these criteria. 2. Please note that if all lighting is full-cutoff, it is permissible to utilize Option 2 on Table 5.1. 3. Please eliminate the redundant ground between the service disconnect and the utility transformer. 4. Please note that Tucson Electric Power Company does not typically provide a 208V, single phase service. Suggest a check with the Developer for this area if this has not already been done. |
| 12/20/2006 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Denied | Special Exception condition #3 for case SE-06-38 specifies that the maximum pole diameter shall be 18 inches. The maximum pole diameter on the drawings and details scales to almost two (2) feet (twenty-four inches). Revise plans to demonstrate compliance by adding a note to the plans stating that the maximum pole diameter shall be 18 inches, and revise dimensions of the "monopalm" in all drawings/details accordingly. |
| 12/20/2006 | TERRY STEVENS | ZONING | REVIEW | Denied | 12/20/06 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The Cell Tower site plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Special Exception section of DSD. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 02/15/2007 | CINDY AGUILAR | REJECT SHELF | Completed |